Doosan DNM6700 TSC MALFUNCTION

Rex_Banner

Plastic
Joined
Jul 12, 2022
Machine is about a year old, just doing short run parts. Now we are running a larger order of thousands of parts, and using through spindle coolant. 2 times now, TSC failed to come on, and the machine did not stop!! When it happens the light on the console will flash, and if I hit that button it will blow a bunch of air, and then trickle out, but it will stop after about 10 seconds. I have to power off the machine to get the coolant back on.

Shouldn't the machine stop when the TSC errors out?? I have seen the same thing on a Haas and it would stop.

It looks like there is a line filter in the tank, and I told the higher ups that it should be cleaned.

Has anyone else had this problem before??

Thank you for your time!!
 

LockNut

Stainless
Joined
Jan 6, 2007
Location
Bergen County
There might be a keep relay that turns on or off the TSC flow sensor. On our DNM5700 it is K11.4. Might be different on yours. Check the blue book that came with the machine. It should be kept in the door of the electrical cabinet.
This may also be caused by low coolant levels too.
 

Rex_Banner

Plastic
Joined
Jul 12, 2022
Thanks for your input, as for the coolant flow issue, I discovered there is a valve on the bottom of the cyclone filter, and that valve needs to be closed, mine was open, and the pressure is now at 20 bar, but I'm still concerned about the machine not stopping if there is a TSC error.

I will check that relay you mentioned
 

Rex_Banner

Plastic
Joined
Jul 12, 2022
Yeah and that's scary!! I have seen a Haas stop dead if the TSC fails, I would think there is a parameter. I really hope!!
 

DouglasJRizzo

Titanium
Joined
Jun 7, 2011
Location
Ramsey, NJ.
The DNM won't stop if the coolant flow isn't up to par.
As long as the controller gets the confirmation that the M8/M7 signal has been sent to the pump(s), that's it.
While you're at it, check the level as well as for clogged screens.
 

Djstorm100

Cast Iron
Joined
Jul 26, 2014
Location
Raleigh NC
The DNM won't stop if the coolant flow isn't up to par.
As long as the controller gets the confirmation that the M8/M7 signal has been sent to the pump(s), that's it.
While you're at it, check the level as well as for clogged screens.
Sounds like a disaster waiting to happen though. At least on the haas it will alarm out because of pressure sensor not seeing TSC pressure.
 

LockNut

Stainless
Joined
Jan 6, 2007
Location
Bergen County
The DNM won't stop if the coolant flow isn't up to par.
As long as the controller gets the confirmation that the M8/M7 signal has been sent to the pump(s), that's it.
While you're at it, check the level as well as for clogged screens.
This is not the case. TSC has a flow sensor. It is really apparent when using tools with really small holes, you will get an alarm. This is why some people disable the flow sensor. There is also an M Code that will temporarily ignore the flow switch. M313 and M314 will turn off/on the flow sensor.
 
Last edited:

Blaser Swisslube

Aluminum
Joined
Jul 30, 2009
Location
Goshen, NY
Machine is about a year old, just doing short run parts. Now we are running a larger order of thousands of parts, and using through spindle coolant. 2 times now, TSC failed to come on, and the machine did not stop!! When it happens the light on the console will flash, and if I hit that button it will blow a bunch of air, and then trickle out, but it will stop after about 10 seconds. I have to power off the machine to get the coolant back on.

Shouldn't the machine stop when the TSC errors out?? I have seen the same thing on a Haas and it would stop.

It looks like there is a line filter in the tank, and I told the higher ups that it should be cleaned.

Has anyone else had this problem before??

Thank you for your time!!
If you haven't already, try to check your pump screens...could be packed with small chips.
 

DouglasJRizzo

Titanium
Joined
Jun 7, 2011
Location
Ramsey, NJ.
This is not the case. TSC has a flow sensor. It is really apparent when using tools with really small holes, you will get an alarm. This is why some people disable the flow sensor. There is also an M Code that will temporarily ignore the flow switch. M313 and M314 will turn off/on the flow sensor.
Cool! Different than the one I was on, although that was a while ago and may have been altered.
 

LockNut

Stainless
Joined
Jan 6, 2007
Location
Bergen County
My AE at Ellison mention some time ago about adding a pressure sensor. Going by his remarks there is no pressure sensor though.
There is no "pressure" sensor. There is a flow sensor, as in GPM. It caused issues when using really small drills with really small coolant holes. It would trigger the flow sensor for lack of flow, based on the setting of the flow switch. There is an M Code for temporary ignoring of the switch. Most people did not know this so they disabled the flow sensor with the keep relay.
 

Djstorm100

Cast Iron
Joined
Jul 26, 2014
Location
Raleigh NC
There is no "pressure" sensor. There is a flow sensor, as in GPM. It caused issues when using really small drills with really small coolant holes. It would trigger the flow sensor for lack of flow, based on the setting of the flow switch. There is an M Code for temporary ignoring of the switch. Most people did not know this so they disabled the flow sensor with the keep relay.
So machines have this keeper relay able or disabled now? How would I check?
 

LockNut

Stainless
Joined
Jan 6, 2007
Location
Bergen County
So machines have this keeper relay able or disabled now? How would I check?
Check in the Blue Book that came with the machine. It has all of the keep relays listed for that machine. It also has all of the parameters and such. This depends on the age of the machine too. Only in the last year or two did we start putting the flow sensors on ALL mills.
 








 